FEATURES:
.128 - .998
Aluminum Body
Smooth Jaws
Threaded Terminal
ELECTRICAL RATINGS:
Continuous current (AMPS) = 350
Fault Current-15 Cycles (AMPS) = 28,000
Fault Current-30 Cycles (AMPS) = 20,000
MECHANICAL RATINGS:
Recommended Torque (in.-lb.) = 250
Main Line Range - Max = 750 kcmil Str. Cu., 636 kcmil, ACSR (.998)
Main Line Range - Min. = #8 Sol. Cu., (.128)
Jumper Range - Max = 2/0 Grd. Cable with threaded ferrule
Jumper Range - Min = #2 Grd. Cable with threaded ferrule
ASTM Designation = Type 1, Class A, Grade 3
|